VTU

Voltage Tracking Unit

Device Description

VTU (Voltage Tracking Unit) is a generation digital input module that provides voltage tracking in single phase or three phase systems. Digital input module has network analyzer specification that provides 4 channel voltage and 3 channel current input on device. In addition to network analyzer and voltage tracking, VTU provides to monitoring of energy parameters of single phase or three phase information that connects. Logical 1 and 0 informations can be set with VTU Configuration Software which voltage range will work. At the same time, power parameter may also be observed which is calculated as real time opening the door to a world of connectivity and control.

 

intelligent devices vtu 3

Device Specification

Supply Voltage Range

9-18 VDC / 18-36 VDC

Nominal Supply Voltage

12 VDC / 24 VDC

CPU

ARM Cortex-M4 32 Bit

Flash

256 kB

Ram

32 kB

Watchdog Timer

System Reset / 5 sec

Power Consumption

1.5W @ 24 V DC

Real Time Clock

Available

Configuration

Inavitas VTU Configuration Software

Communication Specifications

Communication Protocols

Modbus-RTU (Slave) g/n

Serial Interfaces

RS-485 (Isolated), Micro USB Type 2.0

Serial Communication Speed

1200bps – 115200bps

Connection Type

3-Wired (A, B, GND), Semi Duplex

Data Type

8 Bit Data, No Parity, 1 Bit Stop

Insulation

2.5 kVAC RMS 1 Minute

Usb Data Transfer Speed

480 Mbit/s

Digital Input Specifications

Voltage Measurement Range

0 – 275 VAC,RMS

Number of Digital Channels

18 Voltage Inputs

Logical “1” Value

Programmable, Default : ≥ 150VAC,RMS ≤ 275 VAC,RMS

Logical “0” Value

Programmable, Default : ≤ 150VAC,RMS

Input Current

1.5 mA / Channel

Input Filter

Programmable, Default : 100ms

Input Change Counter

32 Bit

Communication Specifications

Communication Protocols

Modbus-RTU (Slave), IEC60870-5-104, IEC62056-21

Serial Interfaces

RS-485, Micro USB C Type 2.0

Serial Communication Speed

1200bps – 115200bps

USB Data Transfer Speed

480 Mbit/s

Power Measurement Specifications

Voltage Measurement Range

0 – 275 VAC,RMS (L – N), 0 – 500 VAC,RMS (L – L)

Curren Measurement Range

1 – 4000 AAC,RMS (Split Type)

Frequency

50 / 60 Hz ±5%

Voltage Channels

3P + N (3 Phase Voltage and Neutral)

Current Channels

3 Current Inputs

Sampling Frequency

128 Sample / Cycle

Voltage Accuracy

±0,5%

Current Accuracy

±1%

Active Energy Accuracy

IEC 62053-22 Class 0.5S

Accuracy Class

IEC 61000-4-30 Class S

Environment Conditions

Operating Temperature

-25°C / +85°C

Storage Temperature

-40°C / +70°C

Operating Humidty

25% – 95% RH

Protection Class

IP20

Mechanical Specifications

Device Dimensions (W x H x D)

35mm x 100mm x 115mm

Weight

150gr